make sure your fuses outside are good if you have any, and make sure that your breaker in the house panel is not tripped for your outside unit. If both of these points are not tripped then you need to see if there is power in your unit when thermostat is on, and make sure your thermostat is clicking on your relay on the outside compressor unit. If all this checks out and there is 240V going through your contactor outside you need to start checking to see if your compressor is bad or if the compressor does turn on then you need to see why it isnt cooling, which may be freon or a safety cutout. | |||
| | |||
| | |||
|
Monday, February 20, 2012
Blower goes on but the air conditioning unit won't go on. What's ...